Data Acquisition

iP-8441-MTCP

• 2 independent Ethernet ports
• Supports Modbus TCP
• Supports Modbus RTU/ASCII
• Supports Modbus TCP to RTU Gateway
• Auto Configuration
• 4 I/O Slots for I-8K and I-87K Series Modules 

Introduction

iP-8441-MTCP series is a Modbus TCP I/O expansion unit to expand I-8K and I-87K series I/O modules over the Ethernet for industrial monitoring and controlling applications. There are more than 50 I/O modules supported with the unit, including analog input/output, digital input/output, counter, frequency I/O modules. It is designed to be used in harsh and noisy environment, so the hardware is manufactured with wide power input range (10 ~ 30 VDC), isolated power input and can operate under wide temperature (-25 ~ +75 °C). To simplify installation and maintenance of I/O modules, it provides many useful features, such as: auto configuration, LED indicators for fault detection, dual watchdog to keep alive, programmable power on and safe values for safety.

Modbus is a very wide known protocol in the industrial manufacturing and environment monitoring fields. Many SCADA software, HMI and PLC has builtin driver to support Modbus devices. Besides, we also provide SDK on different platforms, such as Windows XP, Window CE 5.0/6.0, Linux, MiniOS7. Therefore, it is very easy to integrate remote I/O to customer’s applications. Further more, the iP-8441-MTCP is also a c language based programmable controller that equipped a DOS-like OS (MiniOS7). Programmers can use C compilers that can create 16 bit executable file (*.exe) to customize the Modbus firmware which preinstalled in the iP-8441-MTCP. The SDK provides rich functions for Modbus communication, such as Modbus TCP master/slave, Modbus RTU master/salve, Modbus ASCII master/slave, etc.

Specifications

 Software
 OS MiniOS7
 Development C Language

 

 CPU Module
 CPU 80186 or compatible, 16-bit and 80 MHz
 EEPROM 16 KB
 Flash 512 KB
 NVRAM 31 Bytes
 SRAM 768 KB SRAM, 512 KB Dual battery backup SRAM
 Storage Expansion 4 GB microSD card (up to 32 GB)
 Real Time Clock Provide seconds, minutes, hours, dates, day of week, month, year
 Watchdog Timer Yes

 

 Display
 Type 5 x Digit 7 Segment LED Display

 

 LED Indicators
 Status 1 x Run, 1 x Module offline, 1 x WDT, 1 x Power

 

 I/O Expansion
 I/O Type I-8K, I-87K series
 Slots 4

 

 COM Ports
Ports 2 x RS-232, 1 x RS-485 (3000 VDC Isolated), 1 x RS-232/RS-485
Protocol Modbus RTU/ASCII Slave

 

 HMI
 Buzzer Yes
 DIP Switch 8-bit for address
 Push Button 4

 

 Ethernet
 Ports 2 x RJ-45, 10/100 Base-TX
 Protocol Modbus TCP Slave, Modbus TCP to RTU Gateway

 

 Power
 Input Range +10 ~ 30 VDC (1 kV Isolated )
 Redundant Power Inputs Yes
 Consumption 6.7 W

 

 Mechanical
 Dimensions (mm) 231 x 132 x 111 (W x L x H)
 Installation DIN-Rail, Wall mounting

 

 Environment
 Operating Temperature -25 ~ +75 °C
 Storage Temperature -30 ~ +80 °C
 Humidity 10 ~ 90% RH, Non-condensing

 

Description

 PRODUCT SERIES     DESCRIPTION    QNT   INQUIRY
iP-8441-MTCP     CR  4-slot Modbus TCP I/O Expansion Unit (Modbus TCP Protocol) (RoHS) 1