Data Acquisition

ET-7015

  • Built-in Web Server
  • Web HMI
  • Support for both Modbus TCP and Modbus UDP Protocols
  • Communication Security
  • Dual Watchdog
  • Built-in I/O
    • RTD Input: 7 Channels
 

Introduction

The ET-7015 is specifically designed for long-distance RTD measurement. It features automatic compensation for three-wire RTD regardless of the length of wires and provides open-wire detection for RTD measurement. The ET-7015 offers 7 channels, each of which could be connected with different kinds of RTD (Pt100, Pt1000, Ni120, Cu100, Cu1000). Also, the ET-7015 is fully RoHS-compliant and has qualification for 4 kV ESD protection as well as 2500 VDC intra-module isolation.

Application

Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, and Testing Equipment.

Specifications

 Software
 Built-in Web Server Yes

 

 CPU Module
 Watchdog Timer Module, Communication (Programmable)

 

 Isolation
 2-way Isolation Ethernet: 1500 VDC
I/O: 2500 VDC

 

 EMS Protection
 EFT (IEC 61000-4-4) ±4 kV for Power Line
 ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
±8 kV Air for Random Point
 Surge (IEC 61000-4-5) ±0.5 kV for Power Line

 

 LED Indicators
 Status Run, Ethernet

 

 Analog Input
 Channels 7 (Differential)
 Type RTD (2-wire, 3-wire)
 Sensor Type Pt100, Pt1000, Ni120, Cu100, Cu1000
 Resistance Measurement 3.2 KΩ (max.)
 Resolution 16-bit
 Accuracy ±0.05%
 Sampling Rate 12 Hz (total channels)
 Input Impedance >1M Ω
 Overvoltage Protection +120 VDC
 Individual Channel Configuration Yes
 Open Wire Detection Yes
 3-wire RTD Lead Resistance Elimination Yes

 

 Ethernet
 Ports 1 x RJ-45, 10/100 Base-TX
 Security ID, Password and IP Filter
 Protocol Modbus TCP, Modbus UDP

 

 Power
Reverse Polarity Protection Yes
Consumption 2.2 W (max.)
Powered from Terminal Block +10 to +30 VDC

 

 Mechanical
 Dimensions (mm) 72 x 123 x 35 (W x L x H)
 Installation DIN-Rail mounting

 

 Environment
 Operating Temperature -25 ~ +75 °C
 Storage Temperature -30 ~ +80 °C
 Humidity 10 ~ 90% RH, Non-condensing

 

Description

 PRODUCT SERIES     DESCRIPTION    QNT   INQUIRY
 ET-7015     CR  Ethernet I/O Module with 7-ch RTD Input (RoHS) 1