Data Acquisition

WISE-7102

  • Runs on browsers, no extra software tool is required.
  • No more programming, Web pages provided for control logic editing.
  • IF-THEN-ELSE logic rules execution ability.
  • Built-in I/O (AI: 3-channels; DO: 3-channels Power Relay; DI: 6-channels).
  • Support I/O channel monitoring/control, Timer operations.
  • Support non-SSL Email sending and CGI Command sending operations.
  • Modbus TCP Protocol for SCADA System Integration.
  • IEEE 802.3af-compliant Power over Ethernet (PoE).

Introduction

WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.

WISE-7102 follows IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled network by Ethernet pairs (Category 5 Ethernet cable). This feature provides greater flexibility and higher efficiency therefore simplifying systems design, saving space, reducing cables and eliminating the requirement for dedicated electrical outlets. Meanwhile, in case under a non-PoE environment, WISE-7102 will still be able to receive power from auxiliary power sources like AC adapters or battery, etc.

This multi-function module WISE-7102 supports Modbus/TCP protocol to make seamless integration with SCADA software available. It features 3-channels analog inputs, 6-channels digital inputs and 3-channels Power Relay outputs. Each analog input channel provides 240 Vrms high over voltage protection.
 
 

Application

Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.

Specifications

 Software
 Protocol • Modbus TCP & Modbus RTU
• CGI Command (Sending)
 Function • Web Interface for Configuration
• IF-THEN-ELSE Logic operation (36 rule supported)
• I/O channel monitoring and control
• Timer operation (12 set supported)
• Internal Register operation (48 set supported)
• Recipe operation (12 set supported)
• Advanced P2P (8 set supported)
• non-SSL Email sending function

 

 CPU Module
 CPU 16-bit CPU (80 MHz)

 

 Isolation
 Intra-module Isolation 2500 VDC

 

 EMS Protection
 EFT (IEC 61000-4-4) ±4 kV for Power Line
 ESD (IEC 61000-4-2) ±4 kV Contact for each terminal and ±8 kV Air for random point
 Surge (IEC 61000-4-5) ±0.5 kV for Power Line

 

 LED Indicators
 Status 1 x PoE Power
1 x System Running
1 x Ethernet Link/Act
1 x Ethernet 10/100M Speed

 

 Analog Input
 Channels 3 (Differential)
 Type ±150mv, ±500mv, ±1 V, ±5 V, ±10 V
±20 mA, 0 ~ 20 mA, 4 ~ 20 mA
(Jumper Selectable)
 Resolution 16-bit
 Accuracy ±0.1%
 Sampling Rate 10 Sample/Sec. (Total)
 Input Impedance Voltage: 2 MΩ
Current: 125 Ω
 Common Mode Rejection 86 dB Min.
 Normal Mode Rejection 100 dB
 Overvoltage Protection 240 Vrms
 Overcurrent Protection Yes, 50 mA max. at 110 VDC/VAC max.
 Individual Channel Configuration Yes
 Open Wire Detection Yes, for 4 ~ 20 mA only
 Zero Drift ±20 μV/°C
 Span Drift ±25 ppm/°C

 

 Digital Input/Counter
 Channels 6
 Type Wet Contact
 Sink/Source (NPN/PNP) Sink/Source
 ON Voltage Level +10 VDC ~ +50 VDC
 OFF Voltage Level +4 VDC Max.
 Max. Counts 16-bit (65535)
 Frequency 50 Hz
 Min. Pulse Width 10 ms
 Input Impedance 10 KΩ, 0.5W
 Overvoltage Protection +70 VDC

 

 Relay Output
 Channels 3
 Type Power Relay, Form A (SPST N.O.)
 Contact Rating Operating Voltage Range: 250 VAC/30 VDC
Max Load Current: 5.0A/channel at 25°C
Intra-module Isolation, Field to Logic: 3750 VDC
 Operate Time 6 ms (Typical)
 Release Time 3 ms (Typical)
 Electrical Endurance VDE:
5 A @ 250 VAC 30,000 ops. (10 ops./minute) at 75°C
5 A @ 30 VDC 70,000 ops. (10 ops./minute) at 75°C
UL:
5 A @ 250 VAC/30 VDC 6,000 ops.
3 A @ 250 VAC/30 VDC 100,000 ops.
 Mechanical Endurance 20,000,000 ops. at no load (300 ops./minute)

 

 Ethernet
 Ports RJ-45 x 1, 10/100 Base-TX and automatic MDI/MDI-X
 PoE Yes

 

 Power
 Reverse Polarity Protection Yes
 Input Range 12 ~ 48 VDC
 Consumption 3.4 W
 Powered from PoE Yes, IEEE 802.3af, Class 1
 Powered from Terminal Block Yes, 12 ~ 48 VDC

 

 Mechanical
 Dimensions (mm) 72 x 123 x 35 (W x L x H)
 Installation DIN-Rail Mounting/Wall Mounting

 

 Environment
 Operating Temperature -25 ~ +75 °C
 Storage Temperature -30 ~ +80 °C
 Humidity 10 to 90% RH, Non-condensing

 

Accessories

GPSU06U-6 MDR-20-24 NS-205
GPSU06U-6
MDR-20-24 NS-205

Description

 PRODUCT SERIES     DESCRIPTION    QNT   INQUIRY
GPSU06U-6     CR  Power Supply, 110~240 VAC to 24 VDC/0.25 A, 6 W, two pins USA plug (RoHS) 1