Data Acquisition

M-7011D-G

  • 1 Analog Input
  • Current, Voltage, and Thermocouple Inputs
  • Open Thermocouple Detection
  • High Resolution: 16-bit
  • 50 Hz Event Counter for Digital Input
  • High/Low Alarm for Digital Output
  • Built-in Dual Watchdog

Introduction

The M-7011/M-7011D features current and voltage input as well as thermocouple input. The module provides 1-channel analog input, 1-channel digital input that functions as a 50 Hz event counter, and 2-channel digital output that can be used as a high/low alarm. The module also features open wire detection for the thermocouple input, and 3000 VDC intra-module isolation. The M-7011(D) supports Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7011(D).

Application

• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment

Specifications

CPU Module
Watchdog Timer Module, Communication (Programmable)

 

Display
Type 5-Digit 7 Segment LED Display

 

Isolation
Intra-module Isolation 3000 VDC

 

EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±2 kV Contact for Each Terminal
Surge (IEC 61000-4-5) ±0.5 kV for Power Line

 

LED Indicators
Status 1 x Power and Communication

 

Analog Input
Channels 1 Differential
Type Voltage
Current
Thermocouple
Sensor Type Thermocouple: J, K, T, E, R, S, B, N, C
Range Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V
Current: ±20 mA (requires optional external 125 Ω resistor)
Resolution 16-bit
Accuracy ±0.1% of FSR
Sampling Rate 10 Hz (Total)
Input Impedance > 400 kΩ
Common Voltage Protection ±5 VDC
Overvoltage Protection ±5 VDC
Open Wire Detection For Thermocouple Only

 

Digital Input/Counter
Channels 1
Type Dry Contact
Sink/Source (NPN/PNP) Source
ON Voltage Level Close to GND
OFF Voltage Level Open
Input Impedance 3 kΩ
Overvoltage Protection ±30 VDC

 

Digital Output
Channels 2
Type Open Collector
Sink/Source (NPN/PNP) Sink
Load Voltage +3.5 ~ +30 VDC
Load Current 30 mA/Channel
Power on Value Programmable
Safe Value Programmable

 

COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1)
Protocol Modbus RTU, DCON

 

Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 1.0 W

 

Mechanical
Dimensions (mm) 72 x 123 x 35 (W x L x H)
Installation DIN-Rail Mounting

 

Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing

 

Accessories

        2AB125R

Description

 PRODUCT SERIES     DESCRIPTION    QTY   INQUIRY
 M-7011D-G     CR  1-ch Thermocouple Input Module with LED Display, using DCON and Modbus Protocols (Gray Cover) (RoHS)