Data Acquisition
The I-7063 module provides 8 digital input channels and 3 Form A relay output channels, and the 7065 series provides 4 digital input channels and 5 Form A relay output channels. All digital input channels can be used as 16-bit counters. In addition, the digital input channels can be selected either as sink- or source-type via wire connections. The I-7063D provides 11 LED indicators and the I-7065D/M-7065D provides 9 LED indicators that can be used to monitor the status of the digital input and relay output. The M-7065 supports both the Modbus RTU and DCON protocols, which can be configured via software. There are also options for configuring power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise protection capabilities in industrial environments.
• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment
CPU Module | |
---|---|
Watchdog Timer | Module, Communication (Programmable) |
Display | |
---|---|
Type | I/O LED Indicator |
Isolation | |
---|---|
Intra-module Isolation | 3750 VDC |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±2 kV for Power Line |
ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
LED Indicators | |
---|---|
Status | 1 x Power and Communication 11 x Digital Input/Relay Output |
Digital Input/Counter | |
---|---|
Channels | 8 |
Type | Wet Contact |
Sink/Source (NPN/PNP) | Sink/Source |
ON Voltage Level | +1 VDC Max. |
OFF Voltage Level | +4 ~ +30 VDC |
Max. Counts | 65535 (16-bit) |
Frequency | 100 Hz |
Min. Pulse Width | 5 ms |
Input Impedance | 3 kΩ |
Overvoltage Protection | ±35 VDC |
Relay Output | |
---|---|
Channels | 3 (Form A) |
Type | Power Relay |
Contact Material | Gold-plated Silver Cadmium Alloy |
Contact Rating | 5 A @ 250 VAC 5 A @ 30 VDC |
Operate Time | 6 ms |
Release Time | 3 ms |
Electrical Endurance | 1 x 10^5 ops. |
Mechanical Endurance | 2 x 10^7 ops. |
Power on Value | Programmable |
Safe Value | Programmable |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 ~ 115200 bps |
Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
Protocol | DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | +10 ~ +30 VDC |
Consumption | 1.4 W |
Mechanical | |
---|---|
Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
Installation | DIN-Rail Mounting |
Environment | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -40 ~ +85 °C |
Humidity | 10 ~ 95% RH, Non-condensing |
PRODUCT SERIES | DESCRIPTION | QTY | INQUIRY |
---|---|---|---|
I-7063D CR | 8-ch Isolated (Wet, 4~30 VDC) DI and 3-ch Power Relay Module with LED Display using DCON Protocol (Blue Cover) (RoHS) | 1 |