Data Acquisition

I-7063D

  • 8 Digital Inputs and 3 Relay Outputs
  • Form A Power Relay Output
  • Sink- and Source-type for Digital Input
  • Digital Input Channels Can be Used as 16-bit Counters
  • Configurable Power-on Value and Safe Value Settings
  • Built-in Dual Watchdog

Introduction

The I-7063 module provides 8 digital input channels and 3 Form A relay output channels, and the 7065 series provides 4 digital input channels and 5 Form A relay output channels. All digital input channels can be used as 16-bit counters. In addition, the digital input channels can be selected either as sink- or source-type via wire connections. The I-7063D provides 11 LED indicators and the I-7065D/M-7065D provides 9 LED indicators that can be used to monitor the status of the digital input and relay output. The M-7065 supports both the Modbus RTU and DCON protocols, which can be configured via software. There are also options for configuring power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise protection capabilities in industrial environments.

Application

• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment

Specifications

 CPU Module
 Watchdog Timer Module, Communication (Programmable)

 

 Display
 Type I/O LED Indicator

 

 Isolation
 Intra-module Isolation 3750 VDC

 

 EMS Protection
 EFT (IEC 61000-4-4) ±2 kV for Power Line
 ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
±8 kV Air for Random Point

 

 LED Indicators
 Status 1 x Power and Communication
11 x Digital Input/Relay Output

 

 Digital Input/Counter
 Channels 8
 Type Wet Contact
 Sink/Source (NPN/PNP) Sink/Source
 ON Voltage Level +1 VDC Max.
 OFF Voltage Level +4 ~ +30 VDC
 Max. Counts 65535 (16-bit)
 Frequency 100 Hz
 Min. Pulse Width 5 ms
 Input Impedance 3 kΩ
 Overvoltage Protection ±35 VDC

 

 Relay Output
 Channels 3 (Form A)
 Type Power Relay
 Contact Material Gold-plated Silver Cadmium Alloy
 Contact Rating 5 A @ 250 VAC
5 A @ 30 VDC
 Operate Time 6 ms
 Release Time 3 ms
 Electrical Endurance 1 x 10^5 ops.
 Mechanical Endurance 2 x 10^7 ops.
 Power on Value Programmable
 Safe Value Programmable

 

 COM Ports
 Ports 1 x RS-485
 Baud Rate 1200 ~ 115200 bps
 Data Format (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1)
 Protocol DCON

 

 Power
 Reverse Polarity Protection Yes
 Input Range +10 ~ +30 VDC
 Consumption 1.4 W

 

 Mechanical
 Dimensions (mm) 72 x 123 x 35 (W x L x H)
 Installation DIN-Rail Mounting

 

 Environment
 Operating Temperature -25 ~ +75 °C
 Storage Temperature -40 ~ +85 °C
 Humidity 10 ~ 95% RH, Non-condensing

 

Description

 PRODUCT SERIES     DESCRIPTION    QTY   INQUIRY
 I-7063D     CR  8-ch Isolated (Wet, 4~30 VDC) DI and 3-ch Power Relay Module with LED Display using DCON Protocol (Blue Cover) (RoHS) 1